Cooling maintenance
Cooled doors
Per year
Check if flux is cold after doors. Use thermal camera to check doors temperature.
Encountered problems and solutions
Cooled doors
→ Out air flux is not cold.
Use thermal camera to ensure and compare with other doors.
Inspect water arrival and departure pressure if possible.
Check water quality and PH.
Determine cooled door heat exchanger material and inspect if galvanic corrosion is not occurring.
If blocked, dismount door and purge it. Have a special look on solid particles removed: color and aspect are important indicators to identify problem and prevent future fill.
→ Condensation occur on heat exchanger surface
Humidifier
→ Humidifier is continuously running, or often running (causing electricity, water and maintenance costs)
Check room humidity with a different probe than the one dedicated.
Check room humidity regulation.
Check room air position on humid air chart, and check it doesn’t reach condensation point.
Check room sealing.
→ Humidifier is always/often asking for maintenance
See Humidifier is continuously running, or often running.
Check inlet water quality.
Have the equipment checked by a professional.
Air handling unit
→ Condensation occur on heat exchanger surface
→ Compressor is used even with cold water supply
Check water valves are opened.
Check if probes values are coherent.
Check regulation
If air temperature regulation is too low, unit may use compressor to respond to this high cooling demand.
If humidity in room is too high, unit will condensate only and not lower temperature (i.e. high load).
Check internal pipes are not blocked by a fill.